IMI Eclipse 15mm Straight TRV & Lockshield Pack (9690-63.800)
IMI Hydronic’s thermostatic radiator valve pack, consists of an automatic flow control TRV body, DX head and lockshield. Designed for application in a two-pipe pumped heating system. The required design flow for each radiator is set directly on the Eclipse valve. This automatic flow limitation is done with a twist and the adjusted flow will then not be exceeded. Even if there is an oversupply of pressure, due to load changes in the system, for example other valves closing or during morning start up, Eclipse will guarantee the desired flow. The thermostatic head with our˜incompressible liquid-filled sensor guarantees a reliable and precise room temperature control.
Technical Details & Downloads
Installation manual (PDF download)
Technical manual (PDF download)
Applications area:
Heating systems
Function:
Control
Flow limitation
Shut-off
Dimensions:
DN 15
Pressure class:
PN 10
Temperature:
Max. working temperature: 120°C, with protection cap or actuator 100°C.
Min. working temperature: -10°C.
Flow range Eclipse:
The flow can be stepless pre-set within the range: 10-150 l/h.
Delivery setting: Commissioning
(Max. nominal flow qmN at 10 kPa respecting EN 215: 115 l/h)
Differential pressure (ΔpV) Eclipse:
Max. differential pressure:
60 kPa (<30 dB(A))
Min. differential pressure:
10 – 100 l/h = 10 kPa
100 – 150 l/h = 15 kPa
Materials:
Valve body: Brass
O-rings: EPDM rubber
Valve disc: EPDM rubber
Return spring: Stainless steel
Valve insert: Brass, PPS (polyphenylsulphide)
Spindle: Niro-steel spindle with double O-ring sealing.
Material thermostatic head:
ABS, PA6.6GF30, brass, steel,
Liquid-filled thermostat.
Surface treatment:
Valve body and fittings are nickel-plated.
Marking:
IMI, country code, flow direction arrow, KEYMARK-Designation. II+ Designation.
Orange protection cap.
Standards:
The thermostatic valve bodies meet the following requirements:
– KEYMARK certified and tested to DIN EN 215, series GB.
Pipe connection:
G1/2 male thread with 15 mm compression fitting for copper or precision steel pipe.
Connection to thermostatic head and actuator:
Heimeier M30x1.5
Thermostatic head:
Closed graduation cap and liquid-filled thermostat. High actuating force, minimum hysteresis, optimum closing time. Stable control response even with minor calculated p-band variations (<1 K). Frost protection.
Thermostatic head DX: Setting numbers 0–IIIII. Temperature range 0 °C to 28 °C.
Thermostatic head Halo: Setting numbers I–IIIII. Temperature range 6 °C to 28 °C.